BPD60S3 60KVA 380V Diesel Generator
- Maximum 66kVA Standby, 380V, 1500 RPM
- 135 litre tank : 15 Hours runtime @ 75% load
- Built-in AVR delivers non fluctuating power
- Starter motor 4.5kW 24V Electric Starter
- 4-cylinder 4-stroke Powerful Diesel Engine
- Three Phase Output
- 60kVA Prime Silent Diesel Generator
Prime power (PRP) 60 kVA Standby power (LTP) 66 kVA Power factor 0.8 φ Frequency 50 Hz Voltage 380 V Engine brand FAW Engine model 4DX23-78D-HMS20W Engine Type 4-cylinder 4-stroke Prime Power (kW) 57 Standby Power (kW) 63 Air intake type Turbo & intercooling Cooling mode Water cooling Governor mode Electronic Bore x Stroke(mm) 102x118 Compression ratio 17:1 Rated speed(rpm) 1500 Displacement(L) 3.86 Alternator Alternator 35A 28V Starter Motor Starter motor 4.5kW 24V Description Diesel Generator Generator Controller Datakom D300 Structure Type Silent Noise Level (dBA @ 7m) 72 AVR Constant voltage AVR Excitation Mode Self Excitation Fuel Type Diesel Recommended Oil L-ECD grade or 15W40 ISO9001 Certified Yes CE Certified Yes Alternator Brand Dingol or Equivalent Alternator Model DPC224E Rated Current (A) 100 Amps Per Phase Pole Number 4 Phase Number Three Phase Length 2480 mm Width 950 mm Height 1250 mm Weight 1100 kgs Tank Capacity 135 l Cons. @ 50% Load 5.8 l/h Cons. @ 75% Load 8.6 l/h Cons. @ 100% Load 11.2 l/h Model ATS-BPD-100-3 Poles 4 Phases 3-Ph Rated Current 100A Brand Varta Model 6-QW-60(580)-L Voltage 12V Quantity 2 Capacity 60Ah Dimensions 246*174*190 mm Type Maintenance Free Pre-Delivery Testing
Filled with oil and coolant, tested under full load.YES Pre-Delivery Inspection (PDI)
Full inspection of the generatorYES User Manuals Books supplied & Digital (Online) 24 Hour Telephonic Support YES Type 4-cylinder 4-stroke Air intake type Turbo & intercooling Cooling mode Water cooling Governor mode Electronic Bore x Stroke(mm) 102x118 Compression ratio 17:1 Rated speed(rpm) 1500 Displacement(L) 3.86 Alternator Alternator 35A 28V Starter Motor Starter motor 4.5kW 24V Rated power(without fan)(kW) 57 Standby power(without fan)(kW) 63 Emission compliant Stage II The flywheel shell interface SAE3 Engine with fan Intake and exhaust sysytem: Air filter and connecting pipes;Connecting flang of exhaust pipe Cooling system Cooling system: Radiator with connecting pipes;Fan guard;Belt guard Brand DCP Model DPC224E Prime Capacity (kVA) 60 kVA Power (kW) 48 kW Phases Three Phase Hertz (Hz) 50 Hz RPM 1500 Volts 400 V Power Factor 0.8 Winding No 11 Efficiency (%) 88.6 % Power Input (kW) 54.2 kW Pole Number 4 Wire Material Copper Excitation Self-Excitation Brushes Brushless Auto Voltage Regulator Yes Cooling Air Cooling Current (Ie) 100 A Poles 4 Phases 3-Ph Brand Aisikai Switch Model No SKT1-100A/4P/M1 Interlock Mechanism(s) Mechanical & Electrical Switch Positions Mains / Open / Standby Operation Modes Auto & Manual Current (Ie) 100 A Insulation Voltage (Ui) 750V Impulse Voltage (Uimp) 8KV Switch Copper (Ue) AC440V Conditional Short-circuit Current 10KA Working Voltage AC220V Length 600 mm Depth 330 mm Height 500 mm Weight 21.1 kg 7.12.2 Requirements for alternative sources of supply
- 7.12.2.1 Where any form of alternative supply (emergency supply, UPS etc.), is connected to an electrical installation, a notice to this effect shall be displayed at the main switch of the installation, and where such supply
a) supplies power only to certain circuits in a distribution board, a power-on indicator (visible or audible) shall be provided on each such distribution board as well as a notice indicating that the standby power main switch shall also be switched off in an emergency,
b) only supplies a part of the electrical installation, the notice shall also be displayed on each distribution board in that part of the installation (see 6.6.1.1(d)).
- 7.12.2.2 The means of excitation and commutation shall be appropriate for the intended use of the generating set and the safety and proper functioning of other sources of supply shall not be impaired by the generating plant.
- 7.12.2.3 The prospective short-circuit current and prospective earth fault current shall be assessed for each source of supply or combination of sources, which can operate independently of other sources or combinations. The short-circuit rating of protective devices within the installation and, where appropriate, connected to the main supply, shall not be exceeded for any of the intended methods of operation of the sources.
- 7.12.2.4 Where the alternative supply is intended to provide a supply to an installation that is not connected to the main supply, or to provide a supply as a switched alternative to the main supply, the capacity and operating characteristics of the alternative supply shall be such that danger or damage to equipment does not arise after the connection or disconnection of any intended load as a result of the deviation of the voltage or frequency from the standard range. Means shall be provided to automatically disconnect such parts of the installation, as may be necessary if the capacity of the alternative supply is exceeded.
- 7.12.2.1 Where any form of alternative supply (emergency supply, UPS etc.), is connected to an electrical installation, a notice to this effect shall be displayed at the main switch of the installation, and where such supply
ALL ratings are approximate and at SEA LEVEL. Engines need to be de-rated for altitude. A rough guide to de-rate performance is 1% for every 100m above sea level. I.e: A 20kVA at sea level is an 18kVA at 1000m above sea level (10% less) etc.
The generator will not be able to take the full load instantaneously. The load should be added to the generator gradually. 50% initially and then stepped up over time once engine is up to temperature.