General Engine Data

Engine brandGenerac
Engine modelOVHI V-TWIN
RPM3000
Engine Type2 Cylinder V-Twin OVHI, Air Cooled
Starting System12 Volt Electric Starter
Auto DecompressionYes
Displacement0.999 l
Compression Ratio9.5:1
Engine Power(kW / RPM)
Fuel TypeLPG / NATURAL GAS
Recommended OilMultigrade / 20W50
Low Pressure AlertYes
Low Fuel Cut OutYes
DescriptionGas Generator

General Data

Generator ControllerEvolution
Structure TypeSilent Aluminium Enclosure
Noise Level (dBA @ 7m)65
AVRConstant voltage AVR
Excitation ModeSelf Excitation and Constant Voltage (AVR)
ISO9001 CertifiedYes
CE CertifiedYes

Battery Data

BrandProbe
Model618P
Voltage12V
Quantity1
Capacity38Ah
Dimensions207 x 175 x 175 mm
TypeMaintenance Free

Alternator Data

Alternator ModelGenerac
Rated Current (A)30.4 (LP) / 25.8 (NG) Amps Per Phase
Pole Number2
Phase NumberThree Phase

Generator Dimensions

Length1218 mm
Width638 mm
Height732 mm
Weight210 kgs

We Recommend

Afrox Handigas Premium supplier of Liquid Petroleum Gas (LPG)
Egoli Gas Premium supplier of Natural Gas (NG)

SANS 10142-1:2012

7.12.2 Requirements for alternative sources of supply

  • 7.12.2.1 Where any form of alternative supply (emergency supply, UPS etc.), is connected to an electrical installation, a notice to this effect shall be displayed at the main switch of the installation, and where such supply
    a) supplies power only to certain circuits in a distribution board, a power-on indicator (visible or audible) shall be provided on each such distribution board as well as a notice indicating that the standby power main switch shall also be switched off in an emergency,
    b) only supplies a part of the electrical installation, the notice shall also be displayed on each distribution board in that part of the installation (see 6.6.1.1(d)).
     
  • 7.12.2.2 The means of excitation and commutation shall be appropriate for the intended use of the generating set and the safety and proper functioning of other sources of supply shall not be impaired by the generating plant.
     
  • 7.12.2.3 The prospective short-circuit current and prospective earth fault current shall be assessed for each source of supply or combination of sources, which can operate independently of other sources or combinations. The short-circuit rating of protective devices within the installation and, where appropriate, connected to the main supply, shall not be exceeded for any of the intended methods of operation of the sources.
     
  • 7.12.2.4 Where the alternative supply is intended to provide a supply to an installation that is not connected to the main supply, or to provide a supply as a switched alternative to the main supply, the capacity and operating characteristics of the alternative supply shall be such that danger or damage to equipment does not arise after the connection or disconnection of any intended load as a result of the deviation of the voltage or frequency from the standard range. Means shall be provided to automatically disconnect such parts of the installation, as may be necessary if the capacity of the alternative supply is exceeded.
     
  • 7.12.2.5 Where an alternative supply is provided to an installation or part of an installation as a switched alternative to the main supply, the change-over switching device shall disconnect the main supply before the alternative supply is switched in. The change-over switching device shall be interlocked in such a way that the main supply and the alternative supply cannot be connected to the installation or part of the installation at the same time.
     
  • 7.12.2.6 Except where otherwise permitted in this part of SANS 10142, where a socket-outlet is installed in a circuit on standby power, such circuit shall be protected by an earth leakage protection device with a rated earth leakage tripping current (rated residual current) I∆n not exceeding 30 mA.
     
  • 7.12.2.7 A 230 V generator with a V-O-V earth connection (centre tap on winding which is earthed), shall not be connected to a fixed electrical installation.

Please Note

ALL ratings are approximate and at SEA LEVEL. Engines need to be de-rated for altitude. A rough guide to de-rate performance is 1% for every 100m above sea level. I.e: A 20kVA at sea level is an 18kVA at 1000m above sea level (10% less) etc.

The generator will not be able to take the full load instantaneously. The load should be added to the generator gradually. 50% initially and then stepped up over time once engine is up to temperature.

The BP20S3‑G Gas Generator, Three Phase represents a new generation of reliable, efficient, and durable power solutions. Designed for demanding environments, it delivers consistent performance and exceptional dependability across residential, commercial, and light industrial applications. With a rated three‑phase output, this generator ensures stable electricity supply for sensitive electronics, heavy‑duty equipment, and essential backup systems. Built with advanced engineering and optimized structural integrity, the BP20S3‑G integrates seamlessly into energy setups, equipment upgrades, and specialized applications where uninterrupted power is critical.

At its core, the BP20S3‑G is powered by a fuel‑efficient gas engine that balances strong output with reduced operating costs. The inclusion of Automatic Voltage Regulation (AVR) guarantees stable voltage delivery, protecting connected devices from fluctuations. A user‑friendly digital control panel provides real‑time monitoring, while simplified operation and commissioning reduce installation time. With multiple input/output options and adaptable functionality, the generator is suitable for diverse scenarios requiring precision, responsiveness, and long‑term reliability.

Key Features

  • Rated three‑phase output, ideal for residential, commercial, and industrial use.
  • Compatibility with a wide range of electrical loads, including sensitive electronics and heavy machinery.
  • Fuel‑efficient gas engine designed for durability and reduced running costs.
  • Integrated Automatic Voltage Regulation (AVR) for stable and efficient power delivery.
  • Comprehensive protection functions: overload, short circuit, low oil, and automatic shutdown.
  • Built‑in digital display for monitoring performance and ensuring reliable data exchange.
  • Optimized structural design built on a leading technology platform.
  • Simplified operation and commissioning, reducing installation and setup time.

The BP20S3‑G Gas Generator, Three Phase is engineered to deliver highly integrated solutions for backup power, equipment matching, and energy reliability. Its design emphasizes safety, durability, and ease of use, making it a trusted choice for households, businesses, and industries requiring consistent performance under variable loads. Whether applied in manufacturing, energy, or specialized processes, this generator ensures stable operation, reduced downtime, and long‑term dependability. By combining advanced control functions with robust protection and seamless monitoring, the BP20S3‑G stands out as a powerful solution for modern energy needs.

Additional information

Weight210 kg
20KVA 3Ph Gas

20KVA