Products

BPD150S3 150KVA 380V Diesel Generator

Performance

Prime power (PRP) 150 kVA
Standby power (LTP) 165 kVA
Power factor 0.8 φ
Frequency 50 Hz
Voltage 380 V

General engine data

Engine brand SDEC
Engine model 6HTAA6.5-G21 
Engine Type 6 Cylinder, Water cooled
Prime Power (kW) 137
Standby Power (kW) 151
Air intake type Turbo
Cooling mode Water cooled
Governor mode Electronic
Bore x Stroke(mm) 105 x 124
Compression ratio 16:1
Rated speed(rpm) 1500
Displacement(L) 6.5
Starter Motor 24v
Description Diesel Generator

General data

Generator Controller Datakom D300 
Structure Type Silent
Noise Level (dBA @ 7m) 72
AVR Constant voltage AVR
Excitation Mode Self Excitation
Fuel Type Diesel
Recommended Oil L-ECD grade or 15W40
ISO9001 Certified Yes
CE Certified Yes

Alternator data

Alternator Brand Dingol or Equivalent
Alternator Model DPC274E 
Rated Current (A) 229 Amps Per Phase
Pole Number 4
Phase Number Three Phase

Dimensions & tank

Length 2990 mm
Width 1100 mm
Height 1550 mm
Weight 1783 kgs
Tank Capacity 196 l
Cons. @ 50% Load 14.0 l/h
Cons. @ 75% Load 20.4 l/h
Cons. @ 100% Load 26.9 l/h

Recommended ATS (Auto switch)

Model ATS-BPD-250-3 
Poles 4
Phases 3-Ph
Rated Current 250A

Battery data

Brand Varta
Model 6-QW-80(600)-L
Voltage 12V
Quantity 2
Capacity 80Ah
Dimensions 325*173*226 mm
Type Maintenance Free

Standard features

Pre-Delivery Testing
Filled with oil and coolant, tested under full load.
YES
Pre-Delivery Inspection (PDI)
Full inspection of the generator
YES
User Manuals Books supplied & Digital (Online)
24 Hour Telephonic Support YES

Engine - Specifications

Type 6 Cylinder, Water cooled
Air intake type Turbo
Cooling mode Water cooled
Governor mode Electronic
Bore x Stroke(mm) 105 x 124
Compression ratio 16:1
Rated speed(rpm) 1500
Displacement(L) 6.5
Starter Motor 24v

Engine - Output & consumption

Rated power(without fan)(kW) 137
Standby power(without fan)(kW) 151
Fuel consumption(g/kWh) 30.5 Litres/h
Oil capacity including filter(L) 17.5

Engine - Dimensions

Dry weight of base(kg) 600
Overall dimension(base)(mm) 1330 x 789 x 1079

Alternator - Specifications

Brand DCP
Model DPC274E
Prime Capacity (kVA) 140 kVA
Power (kW) 112 kW
Phases Three Phase
Hertz (Hz) 50 Hz
RPM 1500
Volts 400 V
Power Factor 0.8
Winding No 11
Efficiency (%) 91.7 %
Power Input (kW) 122.1 kW
Pole Number 4
Wire Material Copper
Excitation Self-Excitation
Brushes Brushless
Auto Voltage Regulator Yes
Cooling Air Cooling

ATS - Specifications

Current (Ie) 250 A
Poles 4
Phases 3-Ph
Brand Aisikai
Switch Model No SKT1-250A/4P/M1
Interlock Mechanism(s) Mechanical & Electrical
Switch Positions Mains / Open / Standby
Operation Modes Auto & Manual

ATS - Electrical

Current (Ie) 250 A
Insulation Voltage (Ui) 750V
Impulse Voltage (Uimp) 8KV
Switch Copper (Ue) AC440V
Conditional Short-circuit Current 13KA
Working Voltage AC220V

ATS - Dimensions

Length 600 mm
Depth 330 mm
Height 500 mm
Weight 28 kg

SANS 10142-1:2012

7.12.2 Requirements for alternative sources of supply

  • 7.12.2.1 Where any form of alternative supply (emergency supply, UPS etc.), is connected to an electrical installation, a notice to this effect shall be displayed at the main switch of the installation, and where such supply
    a) supplies power only to certain circuits in a distribution board, a power-on indicator (visible or audible) shall be provided on each such distribution board as well as a notice indicating that the standby power main switch shall also be switched off in an emergency,
    b) only supplies a part of the electrical installation, the notice shall also be displayed on each distribution board in that part of the installation (see 6.6.1.1(d)).
     
  • 7.12.2.2 The means of excitation and commutation shall be appropriate for the intended use of the generating set and the safety and proper functioning of other sources of supply shall not be impaired by the generating plant.
     
  • 7.12.2.3 The prospective short-circuit current and prospective earth fault current shall be assessed for each source of supply or combination of sources, which can operate independently of other sources or combinations. The short-circuit rating of protective devices within the installation and, where appropriate, connected to the main supply, shall not be exceeded for any of the intended methods of operation of the sources.
     
  • 7.12.2.4 Where the alternative supply is intended to provide a supply to an installation that is not connected to the main supply, or to provide a supply as a switched alternative to the main supply, the capacity and operating characteristics of the alternative supply shall be such that danger or damage to equipment does not arise after the connection or disconnection of any intended load as a result of the deviation of the voltage or frequency from the standard range. Means shall be provided to automatically disconnect such parts of the installation, as may be necessary if the capacity of the alternative supply is exceeded.
     
  • 7.12.2.5 Where an alternative supply is provided to an installation or part of an installation as a switched alternative to the main supply, the change-over switching device shall disconnect the main supply before the alternative supply is switched in. The change-over switching device shall be interlocked in such a way that the main supply and the alternative supply cannot be connected to the installation or part of the installation at the same time.
     
  • 7.12.2.6 Except where otherwise permitted in this part of SANS 10142, where a socket-outlet is installed in a circuit on standby power, such circuit shall be protected by an earth leakage protection device with a rated earth leakage tripping current (rated residual current) I∆n not exceeding 30 mA.
     
  • 7.12.2.7 A 230 V generator with a V-O-V earth connection (centre tap on winding which is earthed), shall not be connected to a fixed electrical installation.

Please note

ALL ratings are approximate and at SEA LEVEL. Engines need to be de-rated for altitude. A rough guide to de-rate performance is 1% for every 100m above sea level. I.e: A 20kVA at sea level is an 18kVA at 1000m above sea level (10% less) etc.

The generator will not be able to take the full load instantaneously. The load should be added to the generator gradually. 50% initially and then stepped up over time once engine is up to temperature.

- Maximum 165kVA Standby, 380V, 1500 RPM

- 196 litre tank : 9 Hours runtime @ 75% load

- Built-in AVR delivers non fluctuating power

- 24v Electric Starter

- 6 Cylinder, Water cooled Powerful Diesel Engine

- Three Phase Output

- 150kVA Prime Silent Diesel Generator

Additional information

Weight 1783 kg
Diesel generator KVA

150KVA

Single or Three phase output

Three

Voltage output

380Vac