BPD5000S 5.0KVA 230V Diesel Generator

Performance

Prime power (PRP)4.5 kVA
Standby power (LTP)5.0 kVA
Power factor1 φ
Frequency50 Hz
Voltage230 V

General engine data

Engine brandGeneric
Engine model186FAE 
Engine TypeSingle cylinder: vertical, direct injection
Prime Power (kW)5.9
Standby Power (kW)6.5
Air intake typeNatural
Cooling modeAir
Governor modeMechanical
Bore x Stroke(mm)86 x 72
Compression ratio19:1
Rated speed(rpm)3000
Displacement(L)0.418
Starter Motor12v
DescriptionDiesel Generator

General data

Generator ControllerDatakom DKG-116 
Structure TypeSilent
Noise Level (dBA @ 7m)72
AVRConstant voltage AVR
Excitation ModeSelf Excitation
Fuel TypeDiesel
Recommended OilCD grade or SAE10W-30,15W-40
ISO9001 CertifiedYes
CE CertifiedYes

Alternator data

Alternator BrandGeneric
Alternator ModelTFDY-4.5 
Rated Current (A)21.7 Amps Per Phase
Pole Number2
Phase NumberSingle Phase

Dimensions & tank

Length900 mm
Width520 mm
Height700 mm
Weight150 kgs
Tank Capacity16 l
Cons. @ 50% Load1.2 l/h
Cons. @ 75% Load1.8 l/h
Cons. @ 100% Load2.3 l/h

Recommended ATS (Auto switch)

ModelATS-BP5-11 
Poles2
Phases1-Ph
Rated Current100A

Battery data

BrandCamel
Model6-QW-36
Voltage12V
Quantity1
Capacity36Ah
DimensionsL196*W128*H200 mm
TypeMaintenance Free

Standard features

Pre-Delivery Testing
Filled with oil and coolant, tested under full load.
YES
Pre-Delivery Inspection (PDI)
Full inspection of the generator
YES
User ManualsBooks supplied & Digital (Online)
24 Hour Telephonic SupportYES

Engine - Specifications

TypeSingle cylinder: vertical, direct injection
Air intake typeNatural
Cooling modeAir
Governor modeMechanical
Bore x Stroke(mm)86 x 72
Compression ratio19:1
Rated speed(rpm)3000
Displacement(L)0.418
Starter Motor12v

Engine - Output & consumption

Rated power(without fan)(kW)5.9
Standby power(without fan)(kW)6.5

Alternator - Specifications

BrandGeneric
ModelTFDY-4.5
Prime Capacity (kVA)5.0 kVA
Power (kW)5.0 kW
PhasesSingle Phase
Hertz (Hz)50 Hz
RPM3000
Volts230 V
Power Factor1.0
Rated Current (A)19.57 A
Max Current (A)21.74 A
Performance ClassG1
Insulation ClassF
Protection ClassIP22M
Pole Number2
Wire MaterialCopper
ExcitationSelf-Excitation
BrushesCarbon Brush
Auto Voltage RegulatorYes
CoolingAir Cooling

ATS - Specification

Current (Ie)100 A
Poles2
Phases1-Ph
BrandAisikai
Switch Model NoSKT1-100A/2P
Interlock Mechanism(s)Mechanical & Electrical
Switch PositionsMains / Open / Standby
Operation ModesAuto & Manual
ATS ControllerDatakom DKG-175

ATS - Electrical

Current (Ie)100 A
Insulation Voltage (Ui)750V
Impulse Voltage (Uimp)8KV
Switch Copper (Ue)AC440V
Conditional Short-circuit Current10KA
Working VoltageAC220V

ATS - Dimensions

Length600 mm
Depth330 mm
Height500 mm
Weight22.5 kg

SANS 10142-1:2012

7.12.2 Requirements for alternative sources of supply

  • 7.12.2.1 Where any form of alternative supply (emergency supply, UPS etc.), is connected to an electrical installation, a notice to this effect shall be displayed at the main switch of the installation, and where such supply
    a) supplies power only to certain circuits in a distribution board, a power-on indicator (visible or audible) shall be provided on each such distribution board as well as a notice indicating that the standby power main switch shall also be switched off in an emergency,
    b) only supplies a part of the electrical installation, the notice shall also be displayed on each distribution board in that part of the installation (see 6.6.1.1(d)).
     
  • 7.12.2.2 The means of excitation and commutation shall be appropriate for the intended use of the generating set and the safety and proper functioning of other sources of supply shall not be impaired by the generating plant.
     
  • 7.12.2.3 The prospective short-circuit current and prospective earth fault current shall be assessed for each source of supply or combination of sources, which can operate independently of other sources or combinations. The short-circuit rating of protective devices within the installation and, where appropriate, connected to the main supply, shall not be exceeded for any of the intended methods of operation of the sources.
     
  • 7.12.2.4 Where the alternative supply is intended to provide a supply to an installation that is not connected to the main supply, or to provide a supply as a switched alternative to the main supply, the capacity and operating characteristics of the alternative supply shall be such that danger or damage to equipment does not arise after the connection or disconnection of any intended load as a result of the deviation of the voltage or frequency from the standard range. Means shall be provided to automatically disconnect such parts of the installation, as may be necessary if the capacity of the alternative supply is exceeded.
     
  • 7.12.2.5 Where an alternative supply is provided to an installation or part of an installation as a switched alternative to the main supply, the change-over switching device shall disconnect the main supply before the alternative supply is switched in. The change-over switching device shall be interlocked in such a way that the main supply and the alternative supply cannot be connected to the installation or part of the installation at the same time.
     
  • 7.12.2.6 Except where otherwise permitted in this part of SANS 10142, where a socket-outlet is installed in a circuit on standby power, such circuit shall be protected by an earth leakage protection device with a rated earth leakage tripping current (rated residual current) I∆n not exceeding 30 mA.
     
  • 7.12.2.7 A 230 V generator with a V-O-V earth connection (centre tap on winding which is earthed), shall not be connected to a fixed electrical installation

Please note

ALL ratings are approximate and at SEA LEVEL. Engines need to be de-rated for altitude. A rough guide to de-rate performance is 1% for every 100m above sea level. I.e: A 20kVA at sea level is an 18kVA at 1000m above sea level (10% less) etc.

The generator will not be able to take the full load instantaneously. The load should be added to the generator gradually. 50% initially and then stepped up over time once engine is up to temperature.

 

The BPD5000S 5.0KVA Diesel Generator represents a new generation of reliable, efficient, and durable power solutions. Designed for demanding environments, it delivers consistent performance and exceptional dependability across residential, commercial, and light industrial applications. With a rated output of 5.0KVA at 230V single‑phase, this generator ensures stable electricity supply for sensitive electronics, heavy‑duty equipment, and essential backup systems. Built with advanced engineering and optimized structural integrity, the BPD5000S integrates seamlessly into energy setups, equipment upgrades, and specialized applications where uninterrupted power is critical.

At its core, the BPD5000S is powered by a fuel‑efficient diesel engine that balances strong output with reduced operating costs. The inclusion of Automatic Voltage Regulation (AVR) guarantees stable voltage delivery, protecting connected devices from fluctuations. A user‑friendly digital control panel provides real‑time monitoring, while simplified operation and commissioning reduce installation time. With multiple input/output options and adaptable functionality, the generator is suitable for diverse scenarios requiring precision, responsiveness, and long‑term reliability.

Key Features

  • Rated output of 5.0KVA at 230V single‑phase, ideal for residential and commercial use.
  • Compatibility with a wide range of electrical loads, including sensitive electronics and heavy machinery.
  • Fuel‑efficient diesel engine designed for durability and reduced running costs.
  • Integrated Automatic Voltage Regulation (AVR) for stable and efficient power delivery.
  • Comprehensive protection functions: overload, short circuit, low oil, and automatic shutdown.
  • Built‑in digital display for monitoring performance and ensuring reliable data exchange.
  • Optimized structural design built on a leading technology platform.
  • Simplified operation and commissioning, reducing installation and setup time.

The BPD5000S 5.0KVA Diesel Generator is engineered to deliver highly integrated solutions for backup power, equipment matching, and energy reliability. Its design emphasizes safety, durability, and ease of use, making it a trusted choice for households, businesses, and industries requiring consistent performance under variable loads. Whether applied in manufacturing, energy, or specialized processes, this generator ensures stable operation, reduced downtime, and long‑term dependability. By combining advanced control functions with robust protection and seamless monitoring, the BPD5000S stands out as a powerful solution for modern energy needs.

Additional information

Weight150 kg
Diesel generator KVA

5.0KVA

Single or Three phase output

Single

Voltage output

230Vac